Power Products X1600U Generator Set, equipped with an MTU engine and a LEROY SOMER alternator.
Direct access to sections
GENERAL FEATURES
General characteristics
Description
Power table
Engine type 12V4000G43F
Performance class G3
Frequency (Hz) 60
Reference voltage (V) 480/277
Max ESP power (kVA) 2000
Max ESP power (kWe) 1600
Max PRP power (kVA) 1750
Max PRP power (kWe) 1400
Current (A) 2406
Standard cabinet TERMINAL
Optional cabinet M80
Optional cabinet TELYS
Optional cabinet APM802
Electronic regulation
Mechanically welded chassis with anti-vibration suspensions
Air cooler for temperature range 47/50°C with electric fan
Exhaust compensator(s) with flanges
Starter and charging alternator 24V
Delivered with oil
User manual and commissioning guide
Voltages ESP PRP Amperes
backup
kWe kVA kWe kVA
480/277 1600 2000 1400 1750 2406
440/254 1600 2000 1400 1750 2624
ENGINE FEATURES
General data
Exhaust
Fuel
Oil
Thermal balance
Intake air
Cooling system
Emissions
Engine brand MTU
Engine ref. 12V4000G43F
Aspiration type Turbo
Intake cooling Air/Water DC
Number of cylinders 12
Cylinder arrangement V
Displacement (L) 57.20
Bore (mm) 170
Stroke (mm) 210
Compression ratio 16.5
Speed (RPM) 1800
Piston speed (m/s) 12.60
ESP power (kW) 1672
Regulation class (%) +/- 0.5%
BMEP (bar) 17.70
Regulation type Electronic
Exhaust gas temperature @ ESP 60Hz (°C) 390
Exhaust gas flow @ ESP 60Hz (L/s) 5400
Exhaust back pressure (mm H2O) 500
Consumption 110% (L/h) 391
Consumption 100% load (L/h) 348
Consumption 75% load (L/h) 265
Consumption 50% load (L/h) 188
Max fuel pump flow (L/h) 1500
Oil capacity (L) 260
Min oil pressure (bar) 3.50
Max oil pressure (bar) 7
Oil consumption 100% load (L/h) 1.04
Oil sump capacity (L) 200
Heat rejected in exhaust (kW) 1042
Radiated heat (kW) 75
Heat rejected in water (kW) 560/320
Max intake back pressure (mm H2O) 150
Combustion air flow (L/s) 2100
Engine and radiator capacity (L) 708
Max water temperature (°C) 104
Water outlet temperature (°C) 93
Coolant type Glycol-Ethylene
HT thermostat (°C) 79/92
ALTERNATOR FEATURES
General data
Other data
Brand of alternator LEROY SOMER
Alternator ref. LSA 51.2 S55
Number of phases Three-phase
Power factor (cos Phi) 0.80
Altitude (m) 0 to 1000
Overspeed (rpm) 2250
Number of poles 4
Insulation class H
Temperature class (H/125°) continuous 40°C H / 125°K
AVR type R449
Total Harmonic Distortion no load THD (%)
Waveform: NEMA = TIF
Waveform: IEC = FHT
Number of bearings 1
Direct coupling
Voltage regulation at steady state (+/- %) 0.50
Continuous rated power 40°C (kVA) 2230
Backup power 27°C (kVA) 2453
Efficiency at 100% load (%) 95.50
Air flow (m3/s) 2.80
Short circuit ratio (Kcc) 0.33
Synchronous longitudinal reactance unsaturated (Xd) (%) 374
Synchronous transverse reactance unsaturated (Xq) (%) 224
Transient time constant no load (T'do) (ms) 2660
Saturated transient longitudinal reactance (X'd) (%) 28.30
Transient time constant in short circuit (T'd) (ms) 237
Saturated subtransient longitudinal reactance (X''d) (%) 14.80
Subtransient time constant (T''d) (ms) 22
Subtransient time constant (T''q) (ms) 19
Saturated subtransient transverse reactance (X''q) (%) 18.40
Unsaturated homopolar reactance (Xo) (%) 3.50
Saturated inverse reactance (X2) (%) 16.60
Armature resistance (Ra) (%) 1.60
Armature leakage reactance (Xa) (%) 8.70
Armature time constant (Ta) (ms) 39
No load excitation current (io) (A) 1.30
Load excitation current (ic) (A) 5.60
Load excitation voltage (uc) (V) 64
Response time (Delta U = 20% transient) (ms) 700
Starting (Delta U = 20% permanent or 50% transient) (kVA) 4460
Transient Delta U 4/4 load-Cos Phi 0.8 AR (%) 12.40
No load loss (W) 27100
Heat dissipation (W) 83000
DIMENSIONS
Dimensions compact version
Dimensions soundproof version
Length (mm) 4050
Width (mm) 1885
Height (mm) 2158
Net weight (kg) 11405
Tank capacity (L) 0
Type of soundproofing ISO40 Yes
Length (mm) 12192
Width (mm) 2438
Height (mm) 2896
Net weight (kg) 22260
Tank capacity (L) 500
Sound pressure level @1m dB(A) 93
Sound pressure level @7m dB(A) 85
CABINET
TERMINAL
M80, information reporting
TELYS, ergonomic and user-friendly
APM802 dedicated to energy management
The cabinet serves as a simple terminal for connecting an electrical cabinet.
It offers the following features:
Emergency stop button, customer connection terminal, CE compliance.
The M80 cabinet has a dual function. It serves as a simple terminal for connecting an electrical cabinet and as a dashboard with direct reading, where the dials allow monitoring of the basic parameters of your generator set.
It offers the following features:
Engine parameters: Tachometry, Hour meter, Water temperature indicator, Oil pressure indicator, Emergency stop button, Customer connection terminal, CE compliance.
Extremely versatile, the TELYS cabinet is complete yet remains very accessible due to in-depth work on optimizing ergonomics and user-friendliness. With a large display screen, buttons, and a scrolling wheel, it opts for simplicity and emphasizes communication.
It offers the following features:
Electrical measurements: Voltmeter, Ammeter, Frequency meter.
Engine parameters: Hour meter, Oil pressure, Water temperature, Fuel level, Engine speed, Battery voltage.
Alarms and faults: Oil pressure, Water temperature, No start, Overspeed, Min/max alternator, Min/max battery voltage, Emergency stop, Fuel level.
Ergonomics: Navigation wheel between different menus.
Communication: Remote control and operation software, USB connections, PC connection.
For more information about the product and its options, please refer to the commercial documentation.
The new APM802 control cabinet is dedicated to the operation and monitoring of energy centers for the hospital, data center, banking, oil and gas, industrial, IPP, rental, and mining markets.
This cabinet is standard on all generator sets from 275 kVA intended for coupling functions. For the rest of our range, it is optional.
The human-machine interaction, designed in collaboration with a company specializing in interaction design, facilitates operation with a 100% touch screen. The pre-configured system for energy center applications features a unique customization function compliant with the international standard IEC 61131-3. New communication functions (automation and regulation) enhance the high availability of the installation's equipment.
Highlights:
Dedicated to energy center management.
Ergonomics specially designed
High availability of equipment
Guaranteed modularity and sustainability
Facilitated installation extension
For more information, please refer to the commercial documentation.