Power Products X1540 Generator Set, equipped with an MTU engine and a LEROY SOMER alternator.
Direct access to sections
GENERAL CHARACTERISTICS
General characteristics
Description
Power table
Engine type 12V4000G23R1F
Performance class G3
Frequency (Hz) 50
Reference voltage (V) 400/230
Max ESP power (kVA) 1540
Max ESP power (kWe) 1232
Max PRP power (kVA) 1400
Max PRP power (kWe) 1120
Current (A) 2223
Standard enclosure BORNIER
Optional enclosure M80
Optional enclosure TELYS
Optional enclosure APM802
Electronic regulation
Mechanically welded chassis with anti-vibration suspensions
Air cooler for temperature range 47/50°C with electric fan
Exhaust compensator(s) with flanges
Starter and charging alternator 24V
Delivered with oil
User manual and commissioning guide
Voltages ESP PRP Amperes
backup
kWe kVA kWe kVA
415/240 1232 1540 1120 1400 2143
400/230 1232 1540 1120 1400 2223
380/220 1232 1540 1120 1400 2340
ENGINE CHARACTERISTICS
General data
Exhaust
Fuel
Oil
Thermal balance
Intake air
Cooling system
Emissions
Engine brand MTU
Engine ref. 12V4000G23R1F
Aspiration type Turbo
Intake cooling Air/Water DC
Number of cylinders 12
Cylinder arrangement V
Displacement (L) 57.20
Bore (mm) 170
Stroke (mm) 210
Compression ratio 16.5
Speed (RPM) 1500
Piston speed (m/s) 10.50
ESP power (kW) 1325
Regulation class (%) +/- 0.5%
BMEP (bar) 16.85
Regulation type Electronic
Exhaust gas temperature @ ESP 50Hz (°C) 430
Exhaust gas flow @ ESP 50Hz (L/s) 3400
Exhaust back pressure (mm H2O) 500
Consumption 110% load (L/h) 297
Consumption 100% load (L/h) 273
Consumption 75% load (L/h) 210
Consumption 50% load (L/h) 149
Max fuel pump flow (L/h) 1500
Oil capacity (L) 260
Min oil pressure (bar) 3.50
Max oil pressure (bar) 7
Oil consumption 100% load (L/h) 0.90
Oil sump capacity (L) 200
Heat rejected in exhaust (kW) 686
Radiated heat (kW) 75
Heat rejected in water (kW) 460/170
Max intake back pressure (mm H2O) 150
Combustion air flow (L/s) 1400
Engine and radiator capacity (L) 425
Max water temperature (C°) 104
Water outlet temperature (C°) 100
Coolant type Glycol-Ethylene
HT thermostat (°C) 79/92
Emission PM (g/kW.h) 0.22
Emission CO (g/kW.h) 1.29
Emission HC (g/kW.h) 0.65
ALTERNATOR CHARACTERISTICS
General data
Other data
Commercial brand of the alternator LEROY SOMER
Alternator ref. LSA 50.2 L8
Number of phases Three-phase
Power factor (cos Phi) 0.80
Altitude (m) 0 to 1000
Overspeed (rpm) 2250
Number of poles 4
Insulation class H
Temperature class (H/125°) continuous 40°C H / 125°K
AVR type R450
Total harmonic distortion at no load DHT (%)
Waveform: NEMA = TIF
Waveform: IEC = FHT
Number of bearings 1
Direct coupling
Voltage regulation at steady state (+/- %) 0.50
Continuous rated power 40°C (kVA) 1500
Backup power 27°C (kVA) 1650
Efficiency at 100% load (%) 95.40
Air flow (m3/s) 1.80
Short circuit ratio (Kcc) 0.3150
Unsaturated synchronous longitudinal reactance (Xd) (%) 378
Transient no-load time constant (T'do) (ms) 3910
Saturated transient longitudinal reactance (X'd) (%) 17.40
Transient short circuit time constant (T'd) (ms) 180
Saturated subtransient longitudinal reactance (X''d) (%) 14.80
Subtransient time constant (T''d) (ms) 18
Subtransient time constant (T''q) (ms) 18
Saturated subtransient transverse reactance (X''q) (%) 15.40
Saturated inverse reactance (X2) (%) 15.14
Armature resistance (Ra) (%) 0.0230
Armature leakage reactance (Xa) (%) 0.87
Armature time constant (Ta) (ms) 27
No-load excitation current (io) (A) 0.78
Load excitation current (ic) (A) 3.39
Load excitation voltage (uc) (V) 42.40
Response time (Delta U = 20% transient) (ms) 500
Starting (Delta U = 20% permanent or 50% transient) (kVA) 3082.92
Transient Delta U 4/4 load-Cos Phi 0.8 AR (%) 12
No-load loss (W) 15444.78
Heat dissipation (W) 57480.12
DIMENSIONS
Dimensions compact version
Dimensions soundproof version
Length (mm) 4006
Width (mm) 1885
Height (mm) 2158
Net weight (kg) 10640
Tank capacity (L) 0
Length (mm) 0
Width (mm) 0
Height (mm) 0
Net weight (kg) 0
Tank capacity (L) 0
Sound pressure level @1m dB(A) 0
Guaranteed acoustic power level (Lwa) 0
ENCLOSURE
BORNIER
M80, information reporting
TELYS, ergonomic and user-friendly
APM802 dedicated to energy management
The enclosure serves as a simple terminal for connecting an electrical cabinet.
It offers the following features:
Emergency stop button, customer connection terminal, CE compliance.
The M80 enclosure has a dual function. It serves as a simple terminal for connecting an electrical cabinet and as a direct-reading dashboard with dials that allow monitoring of the basic parameters of your generator set.
It offers the following features:
Engine parameters: Tachometry, Hour meter, Water temperature indicator, Oil pressure indicator, Emergency stop button, Customer connection terminal, CE compliance.
Extremely versatile, the TELYS enclosure is comprehensive yet remains very accessible thanks to in-depth work on optimizing ergonomics and user-friendliness. With a large display screen, buttons, and a scrolling wheel, it opts for simplicity and emphasizes communication.
It offers the following features:
Electrical measurements: Voltmeter, Ammeter, Frequency meter.
Engine parameters: Hour meter, Oil pressure, Water temperature, Fuel level, Engine speed, Battery voltage.
Alarms and faults: Oil pressure, Water temperature, No start, Overspeed, Min/max alternator, Min/max battery voltage, Emergency stop, Fuel level.
Ergonomics: Navigation wheel between different menus.
Communication: Remote control and monitoring software, USB connections, PC connection.
For more information on the product and its options, please refer to the commercial documentation.
The new APM802 control panel is dedicated to the operation and monitoring of energy centers for the hospital, data center, banking, oil and gas, industrial, IPP, rental, and mining markets.
This panel is standard on all generator sets from 275 kVA intended for coupling functions. For the rest of our range, it is optional.
The human-machine interaction, designed in collaboration with a company specializing in interaction design, facilitates operation with a large 100% touch screen. The pre-configured system for energy center applications features a unique customization function compliant with the international standard IEC 61131-3. New communication functions (automation and regulation) enhance the high availability of the installation's equipment.
Highlights:
Dedicated to energy center management.
Ergonomics specifically designed
High availability of equipment
Guaranteed modularity and sustainability
Facilitated installation extension
For more information, please refer to the commercial documentation.