Power Products T1400 Generator Set, equipped with a MITSUBISHI engine and a LEROY SOMER alternator.
Direct access to sections
GENERAL CHARACTERISTICS
General characteristics
Description
Power table
Engine type S12R-PTA
Performance class G3
Frequency (Hz) 50
Reference voltage (V) 400/230
Max power ESP (kVA) 1403
Max power ESP (kWe) 1122.40
Max power PRP (kVA) 1275.50
Max power PRP (kWe) 1020.40
Current (A) 2025
Standard cabinet BORNIER
Optional cabinet M80
Optional cabinet TELYS
Optional cabinet APM802
Electronic regulation
Mechanically welded chassis with anti-vibration suspensions
Radiator for temperature range 48/50°C max with mechanical fan
Fan protection grille and rotating parts (CE option)
Exhaust compensator(s) with flanges
Starter and charging alternator 24V
Delivered with oil and coolant -30°C
User manual and commissioning guide
Voltages ESP PRP Amperes
backup
kWe kVA kWe kVA
415/240 1122 1403 1020 1275 1952
400/230 1122 1403 1020 1275 2025
380/220 1104 1380 1004 1255 2097
ENGINE CHARACTERISTICS
General data
Exhaust
Fuel
Oil
Thermal balance
Intake air
Cooling system
Emissions
Engine brand MITSUBISHI
Engine ref. S12R-PTA
Aspiration type Turbo
Cooling air intake Air/Water DC
Number of cylinders 12
Cylinder arrangement V
Displacement (L) 49.03
Bore (mm) 170
Stroke (mm) 180
Compression ratio 14 : 1
Speed (RPM) 1500
Piston speed (m/s) 9
ESP power (kW) 1220
Regulation class (%) +/- 0.5%
BMEP (bar) 18.11
Regulation type Electronic
Exhaust gas temperature @ ESP 50Hz (°C) 492
Exhaust gas flow @ ESP 50Hz (L/s) 3916
Exhaust back pressure (mm H2O) 600
Consumption at 110% load (L/h) 300
Consumption at 100% load (L/h) 271
Consumption at 75% load (L/h) 208
Consumption at 50% load (L/h) 151
Max fuel pump flow (L/h) 588
Oil capacity (L) 180
Min oil pressure (bar) 2.50
Max oil pressure (bar) 5.80
Oil consumption at 100% load (L/h) 1
Oil sump capacity (L) 150
Heat rejected in exhaust (kW) 758
Radiated heat (kW) 78
Heat rejected in water (kW) 649
Max intake back pressure (mm H2O) 400
Combustion air flow (L/s) 1483
Engine and radiator capacity (L) 300
Max water temperature (°C) 98
Water outlet temperature (°C) 95
Fan power (kW) 30
Fan air flow Dp=0 (m3/s) 25.90
Available back pressure on air (mm H2O) 20
Refrigerant type Glycol-Ethylene
HT thermostat (°C) 82-94
PM emission (g/kW.h) 0.48
CO emission (g/kW.h) 2.36
HC emission (g/kW.h) 0.44
ALTERNATOR CHARACTERISTICS
General data
Other data
Commercial brand of the alternator LEROY SOMER
Alternator ref. LSA 50.2 L7
Number of phases Three-phase
Power factor (cos Phi) 0.80
Altitude (m) 0 to 1000
Overspeed (rpm) 2250
Number of poles 4
Insulation class H
Temperature class (H/125°) continuous 40°C H / 125°K
AVR type R450
Total harmonic distortion at no load THD (%)
Waveform: NEMA = TIF
Waveform: IEC = FHT
Number of bearings 1
Direct coupling
Voltage regulation at steady state (+/- %) 0.50
Continuous rated power 40°C (kVA) 1350
Backup power 27°C (kVA) 1485
Efficiency at 100% load (%) 95.20
Air flow (m3/s) 1.80
Short circuit ratio (Kcc) 0.3440
Unsaturated synchronous longitudinal reactance (Xd) (%) 364
Transient no-load time constant (T'do) (ms) 3750
Saturated transient longitudinal reactance (X'd) (%) 17.40
Transient short circuit time constant (T'd) (ms) 180
Saturated subtransient longitudinal reactance (X''d) (%) 14.80
Subtransient time constant (T''d) (ms) 18
Subtransient time constant (T''q) (ms) 18
Saturated subtransient transverse reactance (X''q) (%) 15.50
Saturated inverse reactance (X2) (%) 15.21
Armature resistance (Ra) (%) 0.0230
Armature leakage reactance (Xa) (%) 0.87
Armature time constant (Ta) (ms) 27
No-load excitation current (io) (A) 0.85
Load excitation current (ic) (A) 3.49
Load excitation voltage (uc) (V) 43.80
Response time (Delta U = 20% transient) (ms) 500
Starting (Delta U = 20% permanent or 50% transient) (kVA) 2766.72
Delta U transient 4/4 load-Cos Phi 0.8 AR (%) 12
No-load loss (W) 15287.43
Heat dissipation (W) 53655.89
DIMENSIONS
Dimensions compact version
Dimensions soundproof version
Length (mm) 4327
Width (mm) 2000
Height (mm) 2365
Net weight (kg) 10076
Tank capacity (L) 0
Length (mm) 0
Width (mm) 0
Height (mm) 0
Net weight (kg) 0
Tank capacity (L) 0
Sound pressure level @1m dB(A) 0
Guaranteed acoustic power level (Lwa) 0
CABINET
BORNIER
M80, information reporting
TELYS, ergonomic and user-friendly
APM802 dedicated to energy management
The cabinet serves as a simple terminal for connecting an electrical cabinet.
It offers the following features:
Emergency stop button, customer connection terminal, CE compliance.
The M80 cabinet has a dual functionality. It serves as a simple terminal for connecting an electrical cabinet and as a direct-reading dashboard with dials that allow monitoring of the basic parameters of your generator set.
It offers the following features:
Engine parameters: Tachymetry, Hour meter, Water temperature indicator, Oil pressure indicator, Emergency stop button, Customer connection terminal, CE compliance.
Extremely versatile, the TELYS cabinet is comprehensive yet remains very accessible due to in-depth work on optimizing ergonomics and user-friendliness. With a large display screen, buttons, and a scrolling knob, it opts for simplicity and emphasizes communication.
It offers the following features:
Electrical measurements: Voltmeter, Ammeter, Frequency meter.
Engine parameters: Hour meter, Oil pressure, Water temperature, Fuel level, Engine speed, Battery voltage.
Alarms and faults: Oil pressure, Water temperature, No start, Overspeed, Min/max alternator, Min/max battery voltage, Emergency stop, Fuel level.
Ergonomics: Navigation knob between different menus.
Communication: Remote control and monitoring software, USB connections, PC connection.
For more information about the product and its options, please refer to the commercial documentation.
The new APM802 control cabinet is dedicated to the operation and monitoring of energy centers for the hospital, data center, banking, oil and gas, industrial, IPP, rental, and mining markets.
This cabinet is standard on all generator sets from 275 Kva intended for coupling functions. For the rest of our range, it is optional.
The human-machine interaction, designed in collaboration with a company specialized in interaction design, facilitates operation with a 100% touch screen. The pre-configured system for energy center applications features a unique customization function compliant with the international standard IEC 61131-3. New communication functions (automation and regulation) enhance the high availability of the installation's equipment.
Highlights:
Dedicated to energy center management.
Ergonomics specifically studied
High availability of equipment
Guaranteed modularity and sustainability
Facilitated installation extension
For more information, please refer to the commercial documentation.