Power Products V550C2 Generator Set, equipped with a VOLVO engine and an alternator.
Direct access to sections
GENERAL FEATURES
General characteristics
Description
Power table
Engine type TAD1641GE
Performance class G3
Frequency (Hz) 50
Reference voltage (V) 400/230
Max power ESP (kVA) 550
Max power ESP (kWe) 440
Max power PRP (kVA) 500
Max power PRP (kWe) 400
Current (A) 794
Standard enclosure TELYS
Optional enclosure APM802
Optional enclosure TERMINAL
Electronic regulation
Mechanically welded chassis with anti-vibration suspensions
Power circuit breaker
Radiator for temperature range 48/50°C max with mechanical fan
Fan protection grille and rotating parts (CE Option)
Silencer attenuation 9dB(A) delivered separately
Charged battery(ies) with electrolyte
Starter and charging alternator 24V
Delivered with oil and coolant -30°C
User manual and commissioning guide
Voltages ESP PRP Amperes
backup
kWe kVA kWe kVA
220 TRI 440 550 400 500 1443
415/240 440 550 400 500 765
400/230 440 550 400 500 794
380/220 440 550 400 500 836
200/115 440 550 400 500 1588
240 TRI 440 550 400 500 1323
230 TRI 440 550 400 500 1381
ENGINE FEATURES
General data
Exhaust
Fuel
Oil
Thermal balance
Intake air
Cooling system
Emissions
Engine brand VOLVO
Engine ref. TAD1641GE
Aspiration type Turbo
Air intake cooling Air/Air DC
Number of cylinders 6
Cylinder arrangement L
Displacement (L) 16.12
Bore (mm) 144
Stroke (mm) 165
Compression ratio 16.5 : 1
Speed (RPM) 1500
Piston speed (m/s) 8.25
ESP power (kW) 484
Regulation class (%) +/- 0.5%
BMEP (bar) 21.88
Regulation type Electronic
Exhaust gas temperature @ ESP 50Hz (°C) 455
Exhaust gas flow @ ESP 50Hz (L/s) 1533
Exhaust back pressure (mm H2O) 1000
Consumption at 110% load (L/h) 112.56
Consumption at 100% load (L/h) 102.05
Consumption at 75% load (L/h) 75.38
Consumption at 50% load (L/h) 51.02
Max fuel pump flow (L/h) 170
Oil capacity (L) 48
Min oil pressure (bar) 0.70
Max oil pressure (bar) 6.50
Oil consumption at 100% load (L/h) 0.10
Oil sump capacity (L) 42
Heat rejected in exhaust (kW) 326
Radiated heat (kW) 20
Heat rejected in water (kW) 184
Max intake back pressure (mm H2O) 500
Combustion air flow (L/s) 633
Engine and radiator capacity (L) 60
Max water temperature (C°) 103
Water outlet temperature (C°) 93
Fan power (kW) 11
Fan air flow Dp=0 (m3/s) 10.90
Available back pressure on air (mm H2O) 30
Refrigerant type Glycol-Ethylene
HT thermostat (°C) 86-96
Emission PM (g/kW.h) 0.086
Emission CO (g/kW.h) 1.15
Emission HC+NOx (g/kW.h) 5.46
Emission HC (g/kW.h) 0.12
ALTERNATOR FEATURES
General data
Other data
Alternator ref. AT02450T
Number of Phases Three-phase
Power Factor (cos Phi) 0.80
Altitude (m) 0 to 1000
Overspeed (rpm) 2250
Number of poles 4
Insulation class H
Temperature class (H/125°) continuous 40°C H / 125°K
AVR type R250
Total Harmonic Distortion at no load THD (%)
Waveform: NEMA = TIF
Waveform: IEC = FHT
Number of bearings 1
Direct coupling
Voltage regulation at steady state (+/- %) 0.50
Continuous rated power 40°C (kVA) 500
Backup power 27°C (kVA) 570
Efficiency at 100% load (%) 94.50
Air flow (m3/s) 0.90
Short circuit ratio (Kcc) 0.4110
Unsaturated synchronous longitudinal reactance (Xd) (%) 307
Unsaturated synchronous transverse reactance (Xq) (%) 184
Transient no-load time constant (T'do) (ms) 1930
Saturated transient longitudinal reactance (X'd) (%) 15.90
Transient short circuit time constant (T'd) (ms) 100
Saturated subtransient longitudinal reactance (X''d) (%) 11.10
Subtransient time constant (T''d) (ms) 10
Subtransient time constant (T''q) (ms) 10
Saturated subtransient transverse reactance (X''q) (%) 14.70
Unsaturated homopolar reactance (Xo) (%) 0.70
Saturated inverse reactance (X2) (%) 12.95
Armature resistance (Ra) (%) 0.0140
Armature leakage reactance (Xa) (%) 0.79
Armature time constant (Ta) (ms) 15
No-load excitation current (io) (A) 0.99
Load excitation current (ic) (A) 3.59
Load excitation voltage (uc) (V) 36
Response time (Delta U = 20% transient) (ms) 500
Starting (Delta U = 20% permanent or 50% transient) (kVA) 1077.06
Transient Delta U 4/4 load-Cos Phi 0.8 AR (%) 14.60
No-load loss (W) 6551.63
Heat dissipation (W) 23152.85
DIMENSIONS
Dimensions compact version
Dimensions soundproof version
Length (mm) 3470
Width (mm) 1500
Height (mm) 2043
Net weight (kg) 3620
Tank capacity (L) 500
Soundproofing type M229
Length (mm) 5031
Width (mm) 1560
Height (mm) 2435
Net weight (kg) 4870
Tank capacity (L) 500
Sound pressure level @1m dB(A) 76
Guaranteed sound power level (Lwa) 97
ENCLOSURE
TELYS, ergonomic and user-friendly
APM802 dedicated to energy center management
TERMINAL
Extremely versatile, the TELYS enclosure is comprehensive yet remains very accessible due to in-depth work on optimizing ergonomics and user-friendliness. With a large display screen, buttons, and a scrolling wheel, it opts for simplicity and emphasizes communication.
It offers the following features:
Electrical measurements: Voltmeter, Ammeter, Frequency meter.
Engine parameters: Hour meter, Oil pressure, Water temperature, Fuel level, Engine speed, Battery voltage.
Alarms and faults: Oil pressure, Water temperature, No start, Overspeed, Min/max alternator, Min/max battery voltage, Emergency stop, Fuel level.
Ergonomics: Navigation wheel between different menus.
Communication: Remote control and monitoring software, USB connections, PC connection.
For more information about the product and its options, please refer to the commercial documentation.
The new APM802 control panel is dedicated to the operation and monitoring of energy centers for the hospital, data center, banking, oil and gas, industrial, IPP, rental, and mining markets.
This panel is standard on all generator sets from 275 kVA intended for coupling functions. For the rest of our range, it is optional.
The human-machine interaction, designed in collaboration with a company specializing in interaction design, facilitates operation with a large 100% touch screen. The pre-configured system for energy center applications features a unique customization function compliant with the international standard IEC 61131-3. New communication functions (automation and regulation) enhance the high availability of the installation's equipment.
Highlights:
Dedicated to energy center management.
Ergonomics specifically designed.
High availability of equipment.
Guaranteed modularity and sustainability.
Facilitated installation extension.
For more information, please refer to the commercial documentation.
The panel serves as a simple terminal for connecting an electrical cabinet.
It offers the following features:
Emergency stop button, customer connection terminal, CE compliance.